FDE Context: Reading Meters at a Real Customer Site
📡 Module 2: Connect & Read Primitives
FDE Context: Reading Meters at a Real Customer Site
You are at a Khazna data centre. They have 4 Schneider PowerLogic meters on their main switchgear, connected via Modbus TCP on the site LAN.
The Real Scenario
The customer gives you:
- Meter IP addresses: 10.0.1.101 through 10.0.1.104
- Modbus port: 502
- Register map: Schneider PM5350 (registers 3000-3060)
Step 1: Verify Network Connectivity
# Can you reach the meters?
for ip in 10.0.1.101 10.0.1.102 10.0.1.103 10.0.1.104; do
echo -n "$ip: "
nc -zv -w 2 $ip 502 2>&1 | grep -o "succeeded\|failed"
doneStep 2: Verify Modbus Communication
# Use the EnergyAtIt historian backfill to test a read
curl -X POST -H "Authorization: $EAT_KEY" \
-H "Content-Type: application/json" \
-d '{"host": "10.0.1.101", "port": 502, "register": 3000}' \
https://app.energyatit.com/api/v1/historian/backfill# Use the EnergyAtIt historian backfill to test a read
curl.exe --% -X POST -H "Authorization: $EAT_KEY" -H "Content-Type: application/json" -d "{"host": "10.0.1.101", "port": 502, "register": 3000}" "https://app.energyatit.com/api/v1/historian/backfill"Step 3: Configure in EnergyAtIt
Once reads work, you register the meters as assets in the platform. From that point on, the platform polls them automatically every 60 seconds.
Common FDE Issues
- Connection refused: Firewall blocking port 502. Ask the customer's IT team.
- Timeout: Wrong IP address or the meter is offline.
- Bad data: Wrong register address. Double-check the manufacturer's register map.
- Intermittent failures: Electrical noise on the RS-485 bus. Suggest shielded cabling.
The terminal is your diagnostic tool. nc, ping, and curl will solve 90% of field issues.