⚡ Power Chain — dc1.5
DC AcademyModule 1: Power Chaindc1.5
Hands-on15 min

Hands-on: Map a Power Chain

⚡ Module 1: Power ChainPrototype

Hands-on: Map a Power Chain

This lesson trains Prototype. Launch opens the public sample hall on the home page. It is a fixed 2×10 sample on the shared floor plan, with a one-line. It is not a connected estate and not a plant you can retune.

What You Will Do

  1. Launch the sample hall
  2. Read the one-line from utility to transformer to UPS A, UPS B, and IT load
  3. Pan and zoom the racks. Select a rack and write down its id and kW
  4. Copy the strip: IT load, PUE, UPS A kW, UPS B kW

Key Things to Observe

  • The one-line is the power chain in miniature: utility, transformation, two UPS paths, then IT
  • PUE on the strip is total facility power divided by IT load. A 10MW facility with 6MW of IT is a PUE of 1.67
  • There is no IT-load slider here. You are reading a sample, not dispatching the plant

Success Criteria

After this exercise you should be able to:

  • Name the hops from utility to IT load
  • Explain why nameplate megawatts are not the same as IT megawatts
  • Say, out loud, that this hall is a sample

The signed-in one-line is a Test surface at /dc/power-path. You can import a panel schedule there. The public home does not upload a spreadsheet. Launch on this lesson still opens the sample hall.

Launch the sample hall, write down the four strip numbers, then come back and mark this lesson complete.

Simulated

Practice a fault, diagnose its cause, and restore your own datacenter.

Open your simulated datacenter

Open Sample hall

Pan the public sample hall and read the one-line. It is a fixed 2×10 sample on the shared floor plan, not a connected estate.

Launch

Log in to track your progress and earn certifications.