Rankings · methodology v1.0
Datacenter operator water and noise responsibility
This sub-view uses the same operators and methodology v1.0. It does not compute a second rank. Noise rules in the appendix are not a score. A complaint is not a finding.
Nobody can pay to change a ranking.
Methodology v1.0, 2026-11-24. Figures retrieved 2026-11-24.
| Composite rank | Operator | WUE | Label | Water stress | Non-potable | Noise disclosure | Official findings |
|---|---|---|---|---|---|---|---|
| 1 | NTT Global Data Centers | 0.38 l/kWh portfolio; 1.24 evaporative Source | Reported (mixed) | Not disclosed Source | Not disclosed | Not disclosed | Not disclosed |
| 2 | Digital Realty | 0.59 Source | Reported | Not disclosed Source | 45% non-potable | Not disclosed | Not disclosed |
| 3 | Equinix | 0.91 (all data centers); 1.41 evaporative Source | Reported | 2,110 ML of 6,040 from high baseline water stress. Not scored as WRI extremely-high. Source | 21% reclaimed | Not disclosed | Not disclosed |
| 4 | Microsoft | 0.27 L/kWh Source | Reported | 50% (6,659 ML) Source | Not disclosed | Not disclosed | Not disclosed |
| 5 | Meta | 0.19 Source | Reported (mixed) | 1,704 / 5,637 ML Source | Not disclosed | Not disclosed | Not disclosed |
| 6 | Alphabet / Google | Not disclosed Source | Not disclosed | High 13% on Google's own scale (low 72%, medium 15%). Not a WRI share. Source | (1,695 + 918) / 13,562 | Not disclosed | Not disclosed |
| 7 | CyrusOne | 0.29 L/kWh, includes restoration Source | Reported | 1,003.4 / 1,311.7 ML. Shown, not min-maxed. Source | Not disclosed | Not disclosed | Not disclosed |
| 8 | Amazon (AWS) | 0.12 L/kWh Source | Reported | 22% high or extremely high, 48% low. WRI 2030 business-as-usual. Not scored. Source | Not disclosed | Not disclosed | Not disclosed |
| 9 | Iron Mountain Data Centers | 0.82 Source | Reported | Not disclosed Source | Not disclosed | Not disclosed | Not disclosed |
| 10 | Apple | Not disclosed Source | Not disclosed | Not disclosed Source | Not disclosed | Not disclosed | Not disclosed |
| 11 | Oracle | Not disclosed Source | Not disclosed | Not disclosed Source | Not disclosed | Not disclosed | Not disclosed |
Pending review
- Alibaba Cloud. No primary report had been reviewed as of the retrieval date.
- IBM. No primary report had been reviewed as of the retrieval date.
- QTS. No primary report had been reviewed as of the retrieval date.
- Switch. No primary report had been reviewed as of the retrieval date.
- Vantage Data Centers. No primary report had been reviewed as of the retrieval date.
Method
Same operators and methodology v1.0 as the composite ranking. WUE is shown with its definition. Unlike definitions are not scored against each other. The noise rows are official rules. They are not a loudness ranking and they are not a finding that a named campus broke a rule. A complaint tally is not a finding.
Nobody can pay to change a ranking.
Local noise rules
Loudoun County, Virginia
For residential properties, the zoning ordinance maximum at the property line is 55 dBA. Data centers submit a pre-construction noise study at site plan and a post-construction study. Complaints go to zoning enforcement. The county says dBA does not capture low-frequency or steady tonal noise well. Comprehensive plan and zoning amendments are anticipated in spring or summer 2027. Code of Virginia section 15.2-2209.5 requires a site assessment and sound profile when a legislative application reasonably anticipates 100 megawatts or more. This is a rule, not a finding about a named site.
Prince William County, Virginia
Chapter 14 changes are effective 1 May 2026. First-time violations are Class 4 misdemeanors. Steady tonal noise, including HVAC, transformers, and backup generators, is defined. Enforcement of those violations is Property Code Enforcement. The hashed county page does not print a numeric sound cap. The ordinance URL returned HTTP 403, so no limit was copied from it. This is not a finding about a named site.
Chandler, Arizona
Ordinance No. 5033 does not set a fixed dBA cap in the sections reviewed. It requires an on-site neighbourhood liaison from 8:00 to 22:00 MST when city staff ask after occupancy, a third-party baseline sound study at the nearest residential or noise-sensitive property line before the first neighbourhood meeting, design so data-center sound does not exceed that baseline, a post-construction peak-operation study, annual peak-operation studies for five years filed within 30 days of the anniversary, and backup-generator tests posted on a public website at least 24 hours ahead.
Granbury, Texas
The city notice says Ordinance 26-14, adopted in April 2026, includes noise mitigation, water-conservation measures, and annual third-party inspections. The linked ordinance PDF returned HTTP 403, so no decibel or equipment duty was copied. The notice is not a finding about a named site.
https://www.granbury.org/CivicSend/ViewMessage/message/292631
Sourced site rows
These rows are supplements. They are not a second score. Only cells re-read from the hashed file are listed.
| Operator | Place | Figure | Label |
|---|---|---|---|
| Ashburn, VA | 76.5 / 23.3 / 53.2Google 2026 Environmental Report | Reported (mixed) | |
| Berkeley County, SC | 988.5 / 86.8 / 901.7Google 2026 Environmental Report | Reported (mixed) | |
| Council Bluffs, IA | 1,746.4 / 400.4 / 1,346.0Google 2026 Environmental Report | Reported (mixed) | |
| The Dalles, OR | 654.3 / 185.3 / 469.0Google 2026 Environmental Report | Reported (mixed) | |
| Douglas County, GA | 440.6 / 73.5 / 367.1Of withdrawal: potable 46.3, reclaimed 394.3Google 2026 Environmental Report | Reported (mixed) | |
| Bristow, VA | 359.6 / 92.0 / 267.6Google 2026 Environmental Report | Reported (mixed) | |
| Dublin, Ireland | 0.5 / 0.4 / 0.1Air-cooled, footnote 226Google 2026 Environmental Report | Reported (mixed) | |
| Eemshaven, Netherlands | 532.2 / 126.5 / 405.7Potable 3.6, non-potable 528.6Google 2026 Environmental Report | Reported (mixed) | |
| Frankfurt, Germany | 1.2 / 1.0 / 0.2Google 2026 Environmental Report | Reported (mixed) | |
| Fredericia, Denmark | 88.8 / 17.0 / 71.8Google 2026 Environmental Report | Reported (mixed) | |
| Hamina, Finland | 4.3 / 3.9 / 0.4Google 2026 Environmental Report | Reported (mixed) | |
| Hanau, Germany | 3.4 / 1.5 / 1.9Google 2026 Environmental Report | Reported (mixed) | |
| Henderson, NV | 401.7 / 162.3 / 239.4Google 2026 Environmental Report | Reported (mixed) | |
| Inzai, Japan | 94.6 / 21.4 / 73.2Google 2026 Environmental Report | Reported (mixed) | |
| Jackson County, AL | 191.0 / 17.4 / 173.6Google 2026 Environmental Report | Reported (mixed) | |
| Lancaster, OH | 307.1 / 171.3 / 135.8Google 2026 Environmental Report | Reported (mixed) | |
| Leesburg, VA | 238.1 / 47.4 / 190.7Google 2026 Environmental Report | Reported (mixed) | |
| Lenoir, NC | 378.3 / 34.0 / 344.3Google 2026 Environmental Report | Reported (mixed) | |
| Lockbourne, OH | 460.8 / 101.3 / 359.5Google 2026 Environmental Report | Reported (mixed) | |
| Mayes County, OK | 1,396.7 / 315.3 / 1,081.4Google 2026 Environmental Report | Reported (mixed) | |
| Mesa, AZ | 19.4 / 9.7 / 9.7Google 2026 Environmental Report | Reported (mixed) | |
| Middenmeer, Netherlands | 13.6 / 4.3 / 9.3Google 2026 Environmental Report | Reported (mixed) | |
| Midlothian, TX | 263.6 / 43.4 / 220.2Google 2026 Environmental Report | Reported (mixed) | |
| Montgomery County, TN | 499.5 / 74.8 / 424.7Google 2026 Environmental Report | Reported (mixed) | |
| Montreal, Canada | 0.3 / 0.2 / 0.1Air-cooled, footnote 228Google 2026 Environmental Report | Reported (mixed) | |
| New Albany, OH | 1,008.1 / 172.4 / 835.7Google 2026 Environmental Report | Reported (mixed) | |
| New Haven, IN | 62.2 / 24.4 / 37.8Google 2026 Environmental Report | Reported (mixed) | |
| Omaha, NE | 241.8 / 57.9 / 183.9Google 2026 Environmental Report | Reported (mixed) | |
| Papillion, NE | 677.8 / 129.6 / 548.2Google 2026 Environmental Report | Reported (mixed) | |
| Pflugerville, TX | 0.4 / 0.3 / 0.1Air-cooled, footnote 229Google 2026 Environmental Report | Reported (mixed) | |
| Phoenix, AZ | 0.5 / 0.4 / 0.1Air-cooled, footnote 230Google 2026 Environmental Report | Reported (mixed) | |
| Quilicura, Chile | 278.2 / 135.2 / 143.0Google 2026 Environmental Report | Reported (mixed) | |
| Red Oak, TX | 67.0 / 16.6 / 50.4Google 2026 Environmental Report | Reported (mixed) | |
| San Bernardo, Chile | 0.9 / 0.8 / 0.1Air-cooled, footnote 231Google 2026 Environmental Report | Reported (mixed) | |
| St. Ghislain, Belgium | 714.4 / 263.6 / 450.8Potable 27.6, non-potable 686.8Google 2026 Environmental Report | Reported (mixed) | |
| Sterling, VA | 258.4 / 58.6 / 199.8Google 2026 Environmental Report | Reported (mixed) | |
| Storey County, NV | 66.7 / 60.0 / 6.7Google 2026 Environmental Report | Reported (mixed) | |
| Sydney, Australia | 1.4 / 1.2 / 0.2Air-cooled, footnote 234Google 2026 Environmental Report | Reported (mixed) | |
| Wilmer, TX | 2.6 / 2.3 / 0.3Air-cooled, footnote 235Google 2026 Environmental Report | Reported (mixed) | |
| Winschoten, Netherlands | 0.1 / 0.05 / 0.05Google 2026 Environmental Report | Reported (mixed) | |
| Other data center locations | 1,020.3 / 101.1 / 919.2Potable 17.4, non-potable 479.1, reclaimed 523.8Google 2026 Environmental Report | Reported (mixed) | |
| Data centers total | 13,562 / 3,039 / 10,523Potable 10,949, non-potable 1,695, reclaimed 918. Golf-course equivalents are not used.Google 2026 Environmental Report | Reported (mixed) | |
| microsoft | Singapore | 338,845 MWh; 423 ML; non-potable 99%Table 15. Section 2 was not in the Deloitte review. A dash in the table means less than 1 ML. Site WUE is not computed from this table.Microsoft 2026 Environmental Data Fact Sheet | Reported (mixed) |
| microsoft | Quincy (WA) | 1,381,569 MWh; 1,292 ML; non-potable 74%Microsoft 2026 Environmental Data Fact Sheet | Reported (mixed) |
| microsoft | San Antonio (TX) | 1,440,710 MWh; 420 ML; non-potable 79%Microsoft 2026 Environmental Data Fact Sheet | Reported (mixed) |
| meta | Data centers total | 4,145 MLCompany withdrawal was 5,637 ML. Construction water of 1,019 ML is excluded from the 2024 totals.Meta 2025 Environmental Data Index | Reported (mixed) |
| meta | Altoona (IA) | Withdrawal 242 ML; location-based Scope 2 666,434 tCO2eMeta 2025 Environmental Data Index | Reported (mixed) |
| meta | Prineville (OR) | 328 MLMeta 2025 Environmental Data Index | Reported (mixed) |
| cyrusone | Portfolio water, unrestored | 1,311.7 / 1,020.9 / 290.9 ML94% of colocation capacity. Restoration was −78.2 ML. Net withdrawal is not the volume used here. CIN4 geothermal is separate.CyrusOne 2025 Sustainability Report | Reported |
| amazon | GLOBAL | PUE 1.14; WUE 0.12AWS official region PUE and WUE CSV | Reported |
| amazon | Europe | PUE 1.11; WUE 0.05AWS official region PUE and WUE CSV | Reported |
| amazon | Middle East | PUE 1.29; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Africa | PUE 1.19; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | North America | PUE 1.14; WUE 0.08AWS official region PUE and WUE CSV | Reported |
| amazon | Central/South America | PUE 1.14; WUE 0.09AWS official region PUE and WUE CSV | Reported |
| amazon | Asia Pacific | PUE 1.25; WUE 1.1AWS official region PUE and WUE CSV | Reported |
| amazon | Europe (Stockholm) | PUE 1.09; WUE 0.02AWS official region PUE and WUE CSV | Reported |
| amazon | Middle East (Bahrain) | PUE 1.33; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Mumbai) | PUE 1.4; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Jakarta) | PUE 1.29; WUE 2.85AWS official region PUE and WUE CSV | Reported |
| amazon | U.S. East (Ohio) | PUE 1.12; WUE 0.06AWS official region PUE and WUE CSV | Reported |
| amazon | Africa (Cape Town) | PUE 1.19; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Europe (Ireland) | PUE 1.1; WUE 0.02AWS official region PUE and WUE CSV | Reported |
| amazon | Middle East (UAE) | PUE 1.25; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Europe (Frankfurt) | PUE 1.24; WUE 0.17AWS official region PUE and WUE CSV | Reported |
| amazon | South America (Sao Paulo) | PUE 1.14; WUE 0.09AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Hyderabad) | PUE 1.43; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | U.S. East (Northern Virginia) | PUE 1.15; WUE 0.06AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Melbourne) | PUE 1.07; WUE 0.06AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Tokyo) | PUE 1.25; WUE 1.22AWS official region PUE and WUE CSV | Reported |
| amazon | U.S. West (Oregon) | PUE 1.12; WUE 0.12AWS official region PUE and WUE CSV | Reported |
| amazon | U.S. West (Northern California) | PUE 1.18; WUE 0.39AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Singapore) | PUE 1.3; WUE 1.57AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Sydney) | PUE 1.14; WUE 0.1AWS official region PUE and WUE CSV | Reported |
| amazon | Canada (Central) | PUE 1.19; WUE 0.06AWS official region PUE and WUE CSV | Reported |
| amazon | Europe (Spain) | PUE 1.06; WUE 0.12AWS official region PUE and WUE CSV | Reported |
| amazon | China (Ningxia) | PUE 1.25; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Canada (West) | PUE 1.13; WUE 0.04AWS official region PUE and WUE CSV | Reported |
| amazon | Europe (London) | PUE 1.23; WUE 0.14AWS official region PUE and WUE CSV | Reported |
| amazon | Europe (Paris) | PUE 1.35; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Middle East (Tel Aviv) | PUE 1.27; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Bangkok) | PUE 1.38; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |
| amazon | Asia-Pacific (Osaka) | PUE 1.46; WUE N/AN/A means no water was used to cool, per the AWS page.AWS official region PUE and WUE CSV | Reported |