Meet the Devices: Substations, BESS, Solar, EVs, Datacenters

⚡ Module 1: Power Grid 101

Meet the Devices: Substations, BESS, Solar, EVs, Datacenters

This lesson introduces the five major device categories you will interact with throughout this course. Each has distinct telemetry profiles, control capabilities, and communication protocols.

Substations

A substation is a node in the grid where voltage is transformed and circuits are switched. Key telemetry points:

  • Bus voltage (per phase, in kV)
  • Line current (per feeder, in A)
  • Real and reactive power (MW and MVAR)
  • Transformer tap position (integer, 1-33 typical)
  • Breaker status (open/closed, binary)
  • Frequency (Hz, measured at the bus)

Protocols used: IEC 61850 MMS for SCADA, IEC 61850 GOOSE for fast tripping (< 4 ms), DNP3 for legacy RTUs.

Battery Energy Storage Systems (BESS)

A utility-scale BESS consists of battery modules, a power conversion system (PCS/inverter), a battery management system (BMS), and thermal management. Key telemetry:

  • State of charge (SOC): 0-100%, the most critical dispatch input
  • State of health (SOH): Remaining capacity relative to nameplate
  • Active power output: MW (positive = discharging, negative = charging)
  • DC bus voltage: Typically 600-1500 VDC
  • Cell temperatures: Per module, in degrees C
  • C-rate: Current charge/discharge rate relative to capacity (1C = full discharge in 1 hour)

Protocols used: Modbus TCP (registers 40001-40100 typical), DNP3, proprietary APIs.

Solar PV Plants

Utility-scale solar installations consist of PV arrays, string inverters or central inverters, combiner boxes, and a plant controller. Key telemetry:

  • AC power output: MW (per inverter and total plant)
  • DC voltage and current: Per string or combiner
  • Irradiance: W/m² from pyranometers
  • Module temperature: Affects efficiency (temperature coefficient: -0.3 to -0.5%/degree C)
  • Curtailment status: Whether the plant is operating below its maximum power point

Protocols used: Modbus TCP, SunSpec alliance standard (Modbus-based), DNP3 for utility interconnection.

Electric Vehicle Charging Infrastructure

EV charging stations range from Level 2 (7-22 kW AC) to DC fast chargers (50-350 kW). Key telemetry:

  • Session status: Available, Preparing, Charging, SuspendedEV, Finishing, Faulted
  • Power delivery: kW per connector
  • Energy delivered: kWh per session
  • Vehicle SOC: If reported by the vehicle (not always available)
  • Connector type: CCS, CHAdeMO, Type 2

Protocols used: OCPP 2.0.1 (WebSocket/JSON), OpenADR 2.0b for demand response signals.

Data Centers

Data centers are among the largest single-point electrical loads, ranging from 5 MW to 500+ MW. Key telemetry:

  • IT load: MW consumed by servers and networking
  • Total facility load: IT load plus cooling, lighting, and losses
  • PUE (Power Usage Effectiveness): Total load / IT load (ideal = 1.0, typical = 1.2-1.6)
  • Cooling system status: Chiller COP, cooling tower approach temperature
  • Backup generator status: Run hours, fuel level, transfer switch position

Protocols used: BACnet/IP for building systems, SNMP for IT equipment, Modbus for power metering, proprietary APIs for workload management.

Each of these device types will appear in your simulator environment, and you will write code that reads from and writes to them using their native protocols.