Telemetry begins with meters -- the instruments that convert physical quantities (voltage, current, power, energy, temperature) into digital values. Understanding meter types, accuracy classes, and data quality issues is essential for building reliable grid software.

Meter Types in the Energy Sector

Revenue meters are the official billing instruments. They measure energy (kWh and kVArh) with high accuracy and are typically certified to IEC 62053 or ANSI C12 standards.

  • Accuracy class 0.2S: Better than +/- 0.2% at rated current. Used for wholesale market settlement.
  • Accuracy class 0.5S: Better than +/- 0.5%. Used for large commercial customers.
  • Accuracy class 1.0: Better than +/- 1.0%. Used for residential and small commercial.

Power quality meters measure voltage, current, power factor, harmonics (up to the 50th harmonic), voltage sags/swells, and flicker. They sample at 256-1024 samples per cycle.

Instrument transformers (CTs and VTs) step down high currents and voltages to measurable levels (typically 5 A and 110 V secondary). Their accuracy class must be considered in the overall measurement chain.

Data Quality Dimensions

Every telemetry value should be evaluated on five dimensions:

  1. Accuracy: Is the value correct within the meter's rated tolerance?
  2. Completeness: Are all expected readings present, or are there gaps?
  3. Timeliness: Did the reading arrive within the expected latency window?
  4. Consistency: Are related values internally consistent (e.g., P = V I PF)?
  5. Validity: Is the value within a physically plausible range?

Common Data Quality Problems

Missing data arises from communication failures, device reboots, or network congestion. Strategies include:

  • Interpolation: Linear interpolation for slowly-changing values (temperature, SOC)
  • Last-known-value (LKV): Carry forward the last reading with a "stale" quality flag
  • Estimation: Use correlated measurements (e.g., estimate solar output from irradiance)

Bad data includes:

  • Stuck values: A meter reporting the same value for an extended period (frozen register)
  • Spike values: A single anomalous reading (often caused by CT saturation or communication errors)
  • Drift: Gradual divergence from the true value (meter calibration degradation)

Quality Flags

Industrial protocols provide built-in quality indicators:

  • IEC 61850: Each data attribute has a q (quality) field with bits for validity, source, test, operator-blocked
  • DNP3: Each point has flags: ONLINE, RESTART, COMM_LOST, REMOTE_FORCED, OVER_RANGE, REFERENCE_ERR
  • Modbus: No built-in quality -- applications must implement their own quality checks

Best Practices

  • Always store the raw value + quality flag + timestamp before any transformations
  • Implement range checks at ingestion: reject values outside physical limits (e.g., frequency > 52 Hz or < 48 Hz)
  • Calculate data completeness ratios per device per hour and alert on drops below 95%
  • Use cross-validation where possible: compare sum of feeder readings against transformer measurement
  • Maintain a data quality dashboard showing completeness heat maps by device and time period