Load Balancing and Peak Shaving
⚙️ Module 4: Grid Operations
Load Balancing and Peak Shaving
Load balancing distributes electrical load across available generation, storage, and controllable loads to maintain system reliability and minimize cost. Peak shaving specifically targets reducing peak demand to avoid expensive peaker generation and demand charges.
The Load Curve
A typical daily load curve for a commercial/industrial facility or grid zone shows:
- Baseload: The minimum load level, typically overnight (midnight to 6 AM)
- Morning ramp: Load increases as businesses open and HVAC starts (6 AM to 10 AM)
- Daytime plateau: Relatively flat load during business hours (10 AM to 4 PM)
- Evening peak: Highest load as residential demand overlaps with commercial (4 PM to 8 PM)
- Evening decline: Load decreases as activity winds down (8 PM to midnight)
In hot climates like the UAE (DEWA), the peak is driven by air conditioning and can reach 2x the baseload. In the US, summer peaks in Texas (ERCOT) regularly stress the grid to its limits.
Peak Shaving Strategies
1. Battery Discharge During Peak
The most direct approach: charge batteries during off-peak hours (when electricity is cheap) and discharge during peak hours (when electricity is expensive or when demand charges apply).
Peak Shaving Savings = Peak Demand Reduction (kW) × Demand Charge ($/kW/month)Example: Reducing peak demand by 500 kW at a demand charge of $15/kW/month saves $7,500/month.
2. Load Shifting
Move flexible loads to off-peak hours:
- EV charging: Delay charging from evening peak (6 PM) to overnight valley (2 AM)
- Thermal storage: Pre-cool buildings in the early morning using ice storage or pre-chilled water
- Industrial processes: Schedule batch processes (smelting, pumping, water treatment) during off-peak
3. On-Site Generation
Dispatch on-site generators (diesel, gas, CHP) during peak periods. In many markets, the cost of running a diesel generator ($0.25-0.40/kWh) is less than peak electricity prices ($0.50-1.00/kWh during scarcity).
4. Demand Response
Curtail non-critical loads in response to grid signals (OpenADR) or price signals:
- HVAC setpoint adjustment (+2 degrees F can reduce cooling load by 10-15%)
- Lighting reduction (dim to 80% in common areas)
- Production slowdown (reduce conveyor speeds, defer non-urgent manufacturing)
Load Balancing Across Phases
Three-phase systems can become unbalanced when single-phase loads are unevenly distributed. Phase imbalance causes:
- Increased losses (neutral current in a 4-wire system)
- Voltage asymmetry (one phase higher, another lower)
- Negative sequence currents that heat rotating machines
The voltage unbalance factor should be kept below 2% per EN 50160:
VUF = V_negative / V_positive × 100%Smart load switches and automatic transfer switches can rebalance loads across phases.
Demand Charge Optimization Algorithm
For a facility with battery storage, the optimal peak shaving algorithm:
- Forecast the next day's load profile (using historical data and weather forecast)
- Set a target peak based on the battery's energy capacity and the expected load shape
- During each interval: If load exceeds the target, discharge the battery to shave the peak down to the target level
- Adjust dynamically: If the battery is depleting too fast, raise the target; if SOC is high at the end of peak, lower the target for the remaining periods
target_peak = max(baseload, peak_load - battery_energy_kWh / peak_hours)This simple algorithm can capture 80-90% of the theoretical maximum savings. More sophisticated approaches use linear programming or reinforcement learning.