Carbon Intensity: Calculating gCO₂/kWh
🌱 Module 6: Carbon & Compliance
Carbon Intensity: Calculating gCO2/kWh
Carbon intensity measures the greenhouse gas emissions produced per unit of electricity generated or consumed. It is expressed in grams of CO2 equivalent per kilowatt-hour (gCO2eq/kWh) and varies dramatically by energy source, location, and time.
Emission Factors by Source
| Energy Source | Direct Emissions (gCO2/kWh) | Lifecycle Emissions (gCO2/kWh) |
|---|---|---|
| Coal | 900-1100 | 950-1200 |
| Natural Gas (CCGT) | 350-450 | 410-520 |
| Natural Gas (Peaker) | 500-700 | 550-750 |
| Oil/Diesel | 650-900 | 700-950 |
| Nuclear | 0 | 5-15 |
| Solar PV | 0 | 25-48 |
| Wind (Onshore) | 0 | 7-15 |
| Wind (Offshore) | 0 | 12-23 |
| Hydroelectric | 0 | 4-30 |
| Geothermal | 0 | 15-55 |
| Battery Storage | 0 (direct) | Depends on charging source |
Direct emissions occur at the point of generation (smokestack). Lifecycle emissions include manufacturing, fuel extraction, transportation, and decommissioning.
Grid Average vs. Marginal Emission Factor
Grid average emission factor: Total emissions divided by total generation. This represents the average carbon intensity of all electricity on the grid at a given time.
Grid Average = Sum(Generation_i × EF_i) / Sum(Generation_i)Marginal emission factor: The emission rate of the next unit of electricity generated (or avoided). This is what changes when you add or remove load.
If adding 1 MW of load causes a gas peaker to increase output:
Marginal EF = 600 gCO2/kWh (peaker emission factor)
If adding 1 MW of load during solar surplus causes no change in fossil generation:
Marginal EF = 0 gCO2/kWhWhich to use? For Scope 2 accounting, use the average factor (or a contract-specific factor). For evaluating the impact of operational decisions (load shifting, DR), use the marginal factor.
Temporal and Locational Carbon Intensity
Carbon intensity varies by:
Time of day:
Midnight: Gas baseload + wind → 300 gCO2/kWh
Noon: Gas baseload + solar + wind → 150 gCO2/kWh
6 PM: Gas baseload + gas peakers → 450 gCO2/kWhLocation: A data center in Norway (hydroelectric grid, ~20 gCO2/kWh) has a dramatically different carbon footprint than one in Poland (coal-heavy grid, ~700 gCO2/kWh).
Calculating Carbon Emissions for a Facility
Emissions (kgCO2) = Energy (kWh) × Carbon Intensity (gCO2/kWh) / 1000
// For time-varying intensity, integrate over each interval:
Total Emissions = Sum over t of (Energy_t × CI_t)For a data center consuming 10 MW:
Hourly energy = 10 MWh = 10,000 kWh
If CI = 400 gCO2/kWh:
Hourly emissions = 10,000 × 400 / 1000 = 4,000 kgCO2 = 4 tonnes CO2
Annual emissions = 4 × 8,760 = 35,040 tonnes CO2Data Sources
- ElectricityMaps: Real-time and forecast carbon intensity for 200+ zones worldwide. API provides 5-minute resolution.
- EPA eGRID: US annual average emission factors by grid region.
- UNFCCC CDM: Standardized baselines for carbon credit projects.
- National registries: DEWA publishes UAE grid emission factors; EU member states report under the EED.
Carbon-Aware Computing
Carbon-aware computing shifts computational workloads to times and locations with lower carbon intensity:
// Simple carbon-aware scheduling
const zones = await getCarbon Intensity(['uae', 'norway', 'ireland']);
const cleanestZone = zones.sort((a, b) => a.intensity - b.intensity)[0];
await migrateWorkload(cleanestZone.id);This can reduce a workload's carbon footprint by 30-50% without increasing cost if compute capacity is available in cleaner regions. EnergyAtIt's workload migration service implements this for data center operators.
Log in to track your progress and earn certifications.